KURT'S LIST of NEED to KNOW FORMULAS for the NEC EXAM
Revised: January, 2011
OHMS LAW AND POWER LAW: NOTE: P = Power in Watts
E = I x R
R = E/I
I = E/R
DC OR SINGLE PHASE : P = E x I = I2 x R THREE PHASE: P = E x I x √3 x P.F.
XL = 2πFL XC = 1 ⁄ (2πFC) Z = √[R2 + (XL – XC)2] In Ohms ( Ω )
1000
%VD = VOLTS DROP
CIRCUIT VOLTAGE
L = LENGTH OF CIRCUIT ONE WAY IN FEET I = CURRENT IN AMPS √3 = 2 x .866
R = RESISTANCE IN OHMS PER 1000 FEET (see NEC Table 8) Sin 600 = .866
SYNCHRONOUS SPEED OF MOTOR:
RPM = 120 x FREQUENCY
# OF POLES
RPM = 60 x FREQUENCY
# OF POLES PAIRS
THREE PHASE VOLT-AMPS: VA = VOLTS X AMPS X √3
  P.F. = TRUE POWER (WATTS)
APPARENT POWER (VA)
P.F. = WATTS
VOLTS x AMPS
P.F. = WATTS 
VOLTS x AMPS x √3
EFFICIENCY: EFF % = OUTPUT (WATTS) NOTE: EFFICIENCY IS ALWAYS LESS THAN 100%
INPUT (WATTS)
HORSEPOWER: NOTE: 746 WATTS = 1 HORSEPOWER
SINGLE PHASE:
THREE PHASE:
MOTOR HP = E x I x EFFICIENCY x P.F.
746
= E x I x EFFICIENCY x P.F. x √3
NEUTRAL LOAD CALCULATION FOR WYE SYSTEM:
Take the SQUARE ROOT of : {[ (A2) + (B2) + (C2) ] - [ (A x B) + (B x C) + (A x C) ]}
NOTE: A, B & C ARE THE CURRENTS IN EACH OF THE THREE PHASES
TRANSFORMER RATIO:
PRIMARY VOLTS x AMPS = SECONDARY VOLTS x AMPS
SECONDARY VOLTS = PRIMARY VOLTS x (SECONDARY TURNS ⁄ PRIMARY TURNS)
BUSS BAR AMPACITY:
COPPER = 1000 AMPS PER SQ. INCH ALUMINUM = 700 AMPS PER SQ. INCH
TRANSFORMER FAULT AMPS (ISC): ISC = IFL ⁄ %Z
IFL = Transformer Full Load Current Base Rating %Z = Percent Impedance (as a decimal)