OHMS LAW AND POWER LAW:                       NOTE: P = Power in Watts

      

E = I x R

R = E/I

I = E/R

DC OR SINGLE PHASE :         P = E x I  = I2 x R                                                    THREE PHASE:   P = E x I x 3 x P.F. 

 
IMPEDANCE & REACTANCE:

                                   XL = 2πFL                  XC = 1 (2πFC)                     Z = √[R2 + (XL – XC)2]            In Ohms ( Ω )

VOLTAGE DROP:
SINGLE PHASE:                                            THREE PHASE:           % OF VOLTAGE DROP:
VOLTS DROP = 2 x L x I x R

                                 1000

                 VOLTS DROP = L x I x R x 3

                                               1000

          %VD = VOLTS DROP 

                   CIRCUIT VOLTAGE   

            

L = LENGTH OF CIRCUIT ONE WAY IN FEET     I  = CURRENT IN AMPS      3 = 2 x .866

R = RESISTANCE IN OHMS PER 1000 FEET (see NEC Table 8)                     Sin 600 = .866

  

                                              SYNCHRONOUS SPEED OF MOTOR:

RPM = 120 x FREQUENCY  

                      # OF POLES 

RPM  =  60 x FREQUENCY 

                 # OF POLES PAIRS

THREE PHASE VOLT-AMPS:     VA = VOLTS X AMPS X 3

  POWER FACTOR (P.F.):                     SINGLE PHASE:       THREE PHASE:

  P.F. = TRUE POWER (WATTS)

                APPARENT POWER (VA) 

                     P.F. =  WATTS

             VOLTS x AMPS

         P.F. =    WATTS 

                VOLTS x AMPS x 3

EFFICIENCY:     EFF % = OUTPUT (WATTS)                      NOTE: EFFICIENCY IS ALWAYS LESS THAN 100%

                                                         INPUT (WATTS)                   

HORSEPOWER:  NOTE:  746 WATTS = 1 HORSEPOWER    

                               SINGLE PHASE:

         THREE PHASE:

                               MOTOR HP = E x I x EFFICIENCY x P.F.  

                                                                        746 

          = E x I x EFFICIENCY x P.F. x 3

                                   746

 NEUTRAL LOAD CALCULATION FOR WYE SYSTEM: 

                                                                  Take the SQUARE ROOT of :   {[ (A2) + (B2) + (C2) ] - [ (A x B) + (B x C) + (A x C) ]}

                                                                  NOTE:  A, B & C ARE THE CURRENTS IN EACH OF THE THREE PHASES

TRANSFORMER RATIO:

PRIMARY VOLTS x AMPS  =  SECONDARY VOLTS x AMPS

SECONDARY VOLTS = PRIMARY VOLTS x (SECONDARY TURNS PRIMARY TURNS)

BUSS BAR AMPACITY:

COPPER = 1000 AMPS PER SQ. INCH          ALUMINUM = 700 AMPS PER SQ. INCH

TRANSFORMER FAULT AMPS (ISC):      ISC = IFL %Z

IFL = Transformer Full Load Current Base Rating                %Z = Percent Impedance (as a decimal)